Let us examine the output transformer No1 which was given as an a recipe for
a good design for a push pull amp of approximately 60 watts in my page on
'Output Transformer Theory'.
First I will display the schematic of OPT No1
:-
Fig1
In the older 2002 edition of my website I list steps 1 to 10 to design OPT
No1. The method was rather vague
and in February 2005 I rationalised the
design process to take all that RDH4 says about OPT design, plus create
a
design flow that lists each step actually required to get to a working design
that any transformer winder can actually
use in his workshop without
any further calculations to produce an OPT.
The main differences between the 2002 method and the 2006 method is that
winding resistance losses are
factored in early after calculating the
primary turns. The primary winding fill factor of the actual core window
size is
limited to to 0.28 x S x T which appears to work with most
OPTs.
Until May 2006, I have not seen any computer program which achieves
what I attempt to achieve by following logic steps and using one's brain, some
intuitive imagination and a pocket calculator with easy equations.
The design logic flow could be used to construct a computer program where one
would enter the design requirements such as power, secondary load, tube Ra, core
dimensions, then with a click on a "design" button, out would come a
terrific design including all the exact wire sizes and a cross sectional drawing
of the bobbin windup details that could be understood easily by anyone with some
winding experience.
Alas, I am not a computer expert, but i can give you the
flow of logic used to get a design finalised.
I invite anyone interested to prepare a PC
program to encompass all the horrible fiddly
details of fitting the wire
that is available from
the suppliers into the cores available for superb OPTs.
OUTPUT TRANSFORMER No1 DESIGN EXAMPLE FOR
60 WATT PP OPT for 5,000 to 6 ohms.
1. Choose tubes, operating conditions and
primary load for the tubes applied across the
full primary, known as the
anode to anode load, PRL, ohms.
**Note.
Careful loadline analysis is required for accurate loading and
is not in this list of steps.
OPT1, One pair of 6550, UL AB1, Ea = 520V, Ia
q = 60mA approx,
so allow for RL =
5ka-a...........................................................................5,000ohms
2. Choose the
secondary nominal speaker load value.
allow a default value of 5 ohms, SRL,
ohms.
OPT1.....................................................................................................5ohms
3. Choose the maximum power at
clipping for the
PRL chosen above. Max PO
for any class of operation, A1, AB1, AB2, watts
**Note. The anode to anode voltage swings can be read off the PP load line
analysis, and PO = ( Vrms anode to anode )
squared / RL
OPT1. PO =
60w.....................................................................................60w
4. Calculate the minimum required core centre
leg cross sectional area, Afe,
for a nearly square core cross
section.
Afe = 300 x sq.rtPO
sq.mm
**Note. This formula has been
derived from a basic formula for
core size used for mains transformers, Afe =
sq.root power input / 4.4
where the Afe is in sq inches. This ancient formula
is based on B being about
1 Tesla at 50Hz but we would want B max < approx
0.5 Tesla for an OPT.
After considerable trials the above formula is a good
guide for audio OPT.
OPT1, Afe = 300 x sq.rt 60 = 300 x 7.75 = 2,323
sq.mm........................2,323sq.mm
5. Calculate the core tongue
dimension, T.
For a square core section, tongue dimension = stack height, ie
T = S.
T x S = Afe, sq.mm
Therefore theoretical T dimension = sq.rt
AFe = th T, mm
eg, thT = sq.rt 2,323 = 48.2
mm............................................................48.2mm
Choose
suitable standard T size from list of available wasteless E&I lamination
core materials.
T sizes commonly
available for OPTs :-
20mm, 25mm, 32mm, 38mm, 44mm, 51mm, 63.5mm
**Note. Choosing a standard T size above
thT gives lower copper winding losses, higher weight,
and choosing T below
thT gives higher losses and lower weight. Afe
will be the same for either 44mm
or 51mm chosen from above so the LF response
won't change with tongue size. HF peformance
depends entirely upon the
interleaving geometry and insulations.
OPT1 choose core T =
44mm..................................................................44mm
6. Calculate theoretical stack
height, thS using the chosen T size.
thS = Afe / T, then adjust to a larger
height to suit nearest standard plastic bobbin size if available,
mm.
OPT1, S = 2,323 / 44 = 52.7mm, but choose
51mm........................................................51mm
7. Adjusted Afe = chosen T x chosen S,
sq.mm
OPT1, Adjusted Afe = 44 x 51 =
2,244sq.mm.................................................................2,244sq.mm
**Note. Some constructors will be using non
wasteless E&I lams,
or C cores which do not have the same relative
dimensions as E&I Wasteless Pattern cores.
The actual sizes of the T, S,
H, & L of the core to be used must be confirmed.
8. Confirm the height of the winding
window, H, mm.
OPT1, 44T wasteless material has H =
22...........................................................................22mm
9. Confirm the length of the
winding widow, L, mm.
OPT1, Wasteless material has L =
66mm............................................................................66mm
10. Calculate the theoretical
primary winding turns, thNp
Np = sq.rt( PRL x PO) x 10,000 / Afe = thNp,
no of turns.
**Note. The formula here is derived from
more complex and complete formula taking B and F
into account. If we assume
magnetic field strength B = 1.6 Tesla, and F = 14 Hz, which is a suitably
low
F for where saturation is commencing, and express V in terms of load and
power,
we get the above short easy equation for primary turns required.
The full formula for calculating B is in step 40 below. The V factor can be
expressed as
sq.root of ( Primary RL x power output ) as in the above
simplified equation.
OPT1, RL = 5,000 ohms, PO = 60w, Afe =
2,244sq.mm from above,
thNp = sq.rt ( 5,000 x 60 ) x 10,000 /
2,244 = 2,440 turns..............................2,440 turns
11. Calculate theoretical Primary
wire dia, thPdia.
**Note 4. The
Primary wire used for the transformer will occupy a portion
of the window
area = 0.28 x L x H. The constant of 0.28 works for 99% of OPT.
Each turn of
wire will occupy an area = oa dia squared.
Overlall or oa dia is
the dia including enamel insulation.
Therefore theoretical over all dia of P wire including
enamel insulation
= sq.rt ( 0.28 x L x H / Np ), mm.
OPT1, thoadia P wire = sq.rt ( 0.28 x 66 x 22 / 2,440
)
= sq.rt
0.167
= 0.4082
mm...............................................................................0.4082mm
12. Find nearest suitable oa wire size
from the tables, oaPdia, mm
OPT1, try oa wire size = 0.414mm, (
for Cudia = 0.355 mm. )..............................0.414mm
13. Establish the bobbin winding
traverse width, Bww, in mm.
**Note 5.
Bobbin traverse width is the distance between the cheek flanges and
varies depending
on who made the bobbin, but each flange thickness = 2mm
maximum is common but could be less.
Where bobbin flanges are not used, and
insulation is simply extended to the full window length L,
the traverse width
will be the same as in the case of of where
bobbin does have flanges.
Ie, the
winding will traverse a distance = L - 4mm.
OPT1, Bww = 66 -
4 = 62
mm...........................................................................62mm
14. Calculate no of theoretical P turns
per layer, thPtpl, turns.
thPtpl = 0.97 x
Bww / oa dia from step 12.
**Note. The constant 0.97 factor allows for
imperfect layer filling.
Leave out fractions of a turn.
OPT1, thPtpl
= 0.97 x 62 / 0.414 =
145.26.........................................................145
turns
15.
Calculate theoretical number of primary layers, thNpl,
then round down
or up to convenient even number of
layers.
Theoretical Npl = thNp /
Ptpl, then round up/down.
OPT1, thNpl = 2,440 / 145 = 16.68
layers; round down to 16................................16 layers
**Note. Rounding down may reduce the Npl needed
for Fs = 14 Hz.
But the actual turns used will still allow Fs = approximately
15 Hz, which is ok.
For those wanting to maintain Fs, or have Fs marginally
lower than 14 Hz,
the Afe can be increased by increasing S from say 51 mm to
62 mm, and still use a standard
sized bobbin, and have Fs at 12Hz.
The
calculated no of primary layers should be an even number to avoid a CT in the
middle of a layer,
and because each 1/2 primary winding must have an equal
number of turns and a symetrical geometric layout
either side of the
CT.
16. Calculate
actual Np.
Np = P layers x
thPtpl
OPT1, Np = 16 x 145 = 2,320
turns...............................................................2,320
turns
17. Calculate
average turn length, TL
TL = ( 3.14 x
H ) + ( 2 x S ) + ( 2 x T ), mm.
OPT1, TL = ( 3.14 x
22 ) + ( 2 x 51 ) + ( 2 x 44 ) = 259
mm............................259mm
18. Calculate primary winding resistance,
Rwp.
Rwp = ( Np x TL ) / ( 44,000 x Pdia
x Pdia ), ohms.
where 44,000 is a constant, and P dia is the copper
dia from the wire tables.
OPT1, Rwp = 2,320 x 267 / ( 44,000 x 0.355 x
0.355 ) = 111.7 ohms................112ohms
19. Calculate primary winding loss
%,
P loss % = 100 x Rwp / ( PRL + Rwp ),
%.
OPT1 P loss = 100 x 112 / ( 5,000 + 112 ) =
2.19%..............................................2.19%
20. Is the winding
loss more than 2.5%? ..................................................yes or
no.
If yes, the design calcs must be checked again, if no, proceed to 21.
OPT1, P winding loss is less than 2.5%.
**Note. If the P winding losses
are less than 2%, there is a possibility that the wire size could be
reduced
to increase the turns per layer, and possibly reduce the number of P
layers by say 2.
However I rarely find P winding losses will be less than 2%
with the rated load, and one must allow for
where RL = 1/2 the design RL
which will double P winding losses.
21. Choose the interleaving pattern
from the list below for the wattage of the transformer.
All OPT will have the
secondary sections containing only one layer of wire.
While this may be
subdivided into further secondary sub sections, there are no designs here which
require
bifilar or trifilar winding or rectangular
wire.
A section of a winding
is defined as a layer or group of layers devoted solely to P or S.
The
term "section" is not to be confused with "layer". For tube OPT, most P sections
will have
more than one layer of wire.
In general, all OPT should comply with the
following P&S layer number relationships :-
Where the first and last winding on is a
primary section, then these sections should have near 1/2 the layers of the
inner sections, hence if there are 3 outer p layers in a P section, the inner
sections might be either 5, 6 or 7 p layers. When this
guide is adhered to
there is the best HF response because the leakage inductance is fairly evenly
and symetrically distributed.
When starting and finishing with an S section
all internal P sections should have the same number of p layers
but it is not
always possible and having say 2 sections of 4 p layers and 2 sections of 5 p
layers is OK.
The size of such "internal sections" should not vary more than
25%. Where such guidelines are adhered to along
with equal thickness
insulations between P and S sections, there are minimal problems with resonances
at HF.
For transformers to suit low drive devices
such as mosfets or transistors, the same amount of interleaving is required for
a
a given power level. The number of p layers will be reduced as Primary RL
becomes low, and wire dia will increase.
An 8 ohm : 8 ohm OPT with very low
dc voltage differences between P and S would have equal numbers of turns for P
and S and perhaps be simply interleaved so each layer of thick wire is
alternatively devoted to either P or S.
The bandwidth can then be very easily
made to go up to 500kHz. As the primary or secondary load is reduced, the effect
of shunt capacitance diminishes, so insulation thickness can be reduced.
Transformers for electrostatic speakers which step up the
amplifier voltage
between 50 and 100 times need to have good insulation for voltages involved and
need to have lower capacitance. They resemble PP OPTs powered "backwards" and
can be designed with the method here.
But for matching tubes to normal 3 to 9 ohm
speaker loads, the interleaving list below with the number of primary layers per
section possible will give at least 70 kHz of bandwidth, and where there is a
highest number of interleavings the bandwidth
can be 300kHz. Using more
interleaving than listed leads to less available room on the bobbin for wire due
to too many layers of insulation, and poor HF due to high shunt capacitances,
and higher winding losses.
For lower Primary RL and higher amplifier power
the larger the OPT becomes and for a given number of interleavings the
HF
response becomes less due to increasing leakage inductance so the larger the OPT
becomes, the number of interleaved sections increases. So a small 15 watt OPT
may only need
3S + 2P sections for 70kHz, but a 500 watt OPT may need 6S +
6P sections.
LIST OF
PRIMARY AND SECONDARY WINDING SEQUENCE ON THE BOBBIN
:-
Up to
15W, 10 to 20 p layers.....S - 5p to 10p - S - 5p to 10p -
S
3S + 2P
sections
2p to 4p
- S - 4p to 8p - S - 4p to 8p - S - 2p to
4p 3S + 4P
15W to 35W,
12 p layers .........2p - S - 4p - S - 4p - S -
2p
3S + 4P
S - 4p - S - 4p - S - 4p -
S
4S + 3P
16 p
layers..........3p - S - 5p - S - 5p - S -
3p
3S + 4P
S - 4p - S - 4p - S - 4p - S - 4p -
S
5S +
4P
2p - S - 4p - S - 4p - S - 4p - S -
2p
4S +
5P
18 p
layers..........3p - S - 6p - S - 6p - S -
3p
3S + 4P
20 p layers.........3p - S - 7p - S - 7p - S -
3p
4S + 3P
S - 5p - S - 5p - S -
5p - S - 5p - S
5S + 4P
2p - S - 5p - S - 6p - S - 5p - S -
2p
4S +
5P
35W to 120W, 14
p layers...........S - 3p - S
- 4p - S - 4p - S - 3p - S
5S +
4P
2p
- S - 3p - S - 4p - S - 3p - S -
2p
4S + 5P
16 p layers............S - 4p - S - 4p - S - 4p - S - 4p -
S
5S +
4P
2p
- S - 4p - S - 4p - S - 4p - S -
2p
4S +
5P
18 p layers............S - 4p - S - 5p - S -
5p - S - 4p -
S
5S +
4P
2p
- S - 5p - S - 4p - S - 5p - S -
2p
4S +
5P
20 p layers............S - 5p - S - 5p - S -
5p - S - 5p -
S
5S +
4P
2p
- S - 5p - S - 6p - S - 5p - S -
2p
4S +
5P
22 p layers............S - 5p - S - 6p - S -
6p - S - 5p -
S
5S +
4P
2p
- S - 6p - S - 6p - S - 6p - S -
2p
4S +
5P
120W to
500W, 10 p layers.........2p - S - 2p - S - 2p - S - 2p - S -
2p
4S +
5P
S - 2p - S - 3p - S - 3p - S - 2p -
S
5S +
4P
1p
- S - 2p - S - 2p - S - 2p - S - 2p - S - 1p
5S + 6P
S - 2p - S - 2p - S - 2p - S - 2p - S - 2p - S
6S + 5P
12 p layers...........2p - S - 3p - S - 2p - S - 3p - S -
2p
4S +
5P
S - 3p - S - 3p - S - 3p - S - 3p -
S
5S +
4P
1p - S - 2p - S - 3p -
S - 3p - S - 2p - S - 1p
5S +
6P
S - 2p - S - 3p - S - 2p - S - 3p - S - 2p -
S
6S + 5P
S - 2p - S - 2p
- S - 4p - S - 2p - S - 2p - S
6S + 5P
14 p layers..........2p - S - 3p - S - 4p -
S - 3p - S - 2p
4S + 5P
S - 3p - S - 4p - S - 4p - S - 3p - S
5S +
4P
1p - S - 3p - S - 3p - S - 3p - S - 3p - S - 1p
5S +
6P
S - 2p - S - 3p - S - 4p - S - 3p - S - 2p - S
6S + 5P
16 p layers............2p - S - 4p - S - 4p
- S - 4p - S -
2p
4S + 5P
S - 4p - S - 4p - S - 4p - S - 4p -
S
5S +
4P
2p - S - 3p - S - 3p -
S - 3p - S - 3p - S - 2p
5S +
6P
S - 3p - S - 3p - S - 4p - S - 3p - S - 3p - S
6S + 5P
18 p layers............2p - S - 5p - S - 4p -
S - 5p - S -
2p
4S + 5P
S - 5p - S - 4p - S - 4p - S - 5p -
S
5S +
4P
2p - S - 4p - S - 3p -
S - 3p - S - 4p - S - 2p
5S +
6P
S - 3p - S - 4p - S - 4p - S - 4p - S - 3p - S
6S + 5P
20 p layers............3p - S - 5p - S - 4p - S - 5p - S -
3p
4S + 5P
S - 5p - S - 5p - S - 5p - S - 5p -
S
5S +
4P
2p - S - 4p - S - 4p -
S - 4p - S - 4p - S - 2p
5S +
6P
S - 4p - S - 4p - S - 4p - S - 4p - S - 4p -
S
6S + 5P
22 p layers.............3p - S - 5p - S - 6p - S - 5p - S -
3p
4S + 5P
S - 5p - S - 6p - S - 6p - S - 5p -
S
5S +
4P
2p - S - 5p - S - 4p -
S - 4p - S - 5p - S - 2p
5S +
6P
S - 4p - S - 6p - S - 4p - S - 6p - S - 4p -
S
6S + 5P
Record
the choice of primary layers in step 15.
choose a suitable P& S
interleaving pattern from the above list.
OPT1, 16 primary layers, 60 watts, choose
...............................................................4S + 5P.
22. Choose insulation, i, in mm used
between primary layers, mm.
**Note.
Usually p to p insulation for all OPT
needs to only be 0.05mm thick.
OPT1, i =
0.05mm....................................................................................................0.05mm
23. Choose insulation, I,
in mm used between Primary and Secondary layers, mm.
**Note. Usually, for where Ea is
above 450V, and RL above 1k, the p to S
insulation is first reckoned = 0.6mm
to keep shunt capacitance low with good enough
insulation.
OPT1, I =
0.6 mm
...................................................................................................0.6mm
24. Calculate portion of bobbin
winding height comprising primary wire layers, p to p insulation,
and p to S
insulation.
height of P+I+i = ( no of layers
x oadia P wire ) + ( no x i ) + ( no x I ), mm.
OPT1, P = 16 x
0.414 = 6.624 mm,
i ht = 11 x
0.05 = 0.55 mm,
I ht = 8 x
0.6 = 4.8 mm,
Total ht of above = 11.974
mm............................................................................11.98mm
25. Calculate maximum total available
height of all windings on bobbin.
Max
wind ht = 0.8 x H, mm.
**Note.
The constant of 0.8 will suit most OPT.
OPT1, Wht = 0.8 x 22 =
17.6
mm...................................................................................17.6mm
26. Calculate the max theoretical
oa dia of the the secondary wire in secondary layers, thSoadia.
max thSoadia = ( max wind ht - [ P+i+I ht ] ) /
no of S layers, mm
**Note. The available height for secondary layers = maximum bobbin winding
height - ( primary + all insulations ).
OPT1, We have chosen 4 layers of secondary wires. Height from step 24 =
11.98mm
thSoadia = ( 17.6 - 11.98 ) / 4 = 5.62 / 4 = 1.405
mm..............................................1.406mm
27. Find nearest oa dia wire size
less than thSoadia calculated in step 26.
OPT1, Try 1.351mm oa dia, which is 1.25 mm Cu dia
...............................................1.351mm
28. Calculate the theoretical
S turns per layer, to nearest turn, thStpl.
Get the Bobbin winding width from
step 13, Bww.
Theoretical
S turns per layer, thStpl = Bww /
thSoadia from step 27
OPT1, thStpl = 62 / 1.351 = 45.89, choose
45...........................................................45 turns per
layer
**Note.
The calculated turns per layer are for the thickest wire possible but could be
more turns of a smaller dia
to obtain the wanted turn ratios to to give the
wanted load matches.
No less than 45 turns per S layer can be used if
the traverse width is kept full because the increase in wire size will give a
total height of the winding which exceeds the allowable total winding
height.
29. Calculate
the nearest full S turns needed for loads of 3.5 ohms, 5 ohms and 7
ohms.
Secondary turns = primary turns /
square root of impedance ratio.
OPT3, 2,320 P turns. PRL = 3.1k ,
for 3.5 ohms want 61 turns,
for 5.0
ohms want 73 turns,
for 7.0 ohms want 87 turns.
30.
Choose a pattern of Secondary winding sections from Fig 2, 3, 4, 5 below to
possibly give a suitable variety
of at least two secondary load matches of
between 3 and 9 ohms to suit most modern speakers
while the Primary load is considered to be 5,000
ohms.
OPT1, From step 15 we caculated 16 primary layers.
In the
P&S winding list in step 21 we selected the 5S + 5P winding pattern.
See Fig3 below.
Reading the charts below could be
confusing!!!
Each rectangle represents a given separate OPT . The
figure of N and its multiples are shown to give the
relationship between
numbers of turns in each winding shown as a thick line.
Consider example 2A
in Fig2..
There are two layers, each divided into 2N and N turns, which means
there could be 50 and 25 turns respectively.
Where it says "3 @ 2N" means
there are 3 parallel windings of 2N turns each
In the case of 2A, it means
there are in fact 2 windings of 2N each and the third is made up of N+N in
series.
Ns, or the secondary turn number for the transformer = 2N turns,
since paralleling any number of same turn windings
does not alter Ns .
"2
@ 3N consists of two parallel windings each consisting of 2N + N turns in
series.
In the case of all transformers the first line of impedance loads are
listed for a given number
of N as "Z = 1.0 1.7
3.0 5.0" , and the figures are starting reference impedances for
each transformer.
The next line below for an increased number of N give the
relative values of Z for that number of N
and the vertical columns of Z
values give the relative impedance relationships for the various numbers of
N
in windings.
So reading 2A, if we have 1.0 ohms as the match possible
for 2N turns, then for 3N turns
the match is for 2.3 ohms, and for 6N turns
the match is to 9 ohms.
There could also be a match where 2N = 3.0 ohms, and
reading down the figures 3N gives 6.8 ohms, 6N gives 27 ohms.
In 2B, there is 4 @ 1N, Z = 1.0, etc, but
the figure of N for 2A and 2B have no relationship.
I hope I have made
it easy for everyone to get easy valuable winding information.
Fig
2. Fig 3. Fig 4. Fig 5.




Each rectangle represents the secondaries in a given OPT. There is no need
to include the primary layers because
the number of primary layers could
vary hugely without any change to the secondary layout ans sub section
divisions.
The secondaries are always going to have turns appropriate to
relatively low loads in the majority of OPT.
For the OPT No1 example we have chosen to use 4S + 5P so we can trial the
secondary subsections
from any of the 3 examples of 4A, 4B, or 4C shown in
the above Fig 3. We have already calculated in step 28
that we could possibly have 45 turns per
layer.
Compare all available arrangements of secondary sub-sections and
decide which arrangement offers the most useful
range of load
matches.
OPT1,
Examine 4A from Fig3.
There is a total of 6 windings with the
numerical relationships of 3 windings of N turns, and 4 windings of 3N
turns.
So we can have the top S layer divided into 3 windings of 15 turns
each and 3 other layers of 45 turns each.
This allows the connection of windings to be
as follows :-
4 parallel windings of 45 turns as calculated in step
29.........................................1.88 ohms
3 parallel windings of 60 turns consisting of 45 + 15 turns
each............................3.34 ohms
2 parallel windings of 90 turns
each consisting of 2 x 45 turns in series.................7.52 ohms
4
series windings of 45 turns each = 180turns
.....................................................30.1 ohms
The above selection has two load matches
between 3 ohms and 9 ohms.
**Note. The calculated number of turns
per layer of 45 just happens to be exactly divisible by 3.
If the layer was
not exactly divisible, say it was 41, 44, 46, or 47 turns, we would be forced to
adjust the turns
to the next highest number
of turns divisible by 3, and revise our load match
calculations.
Examine 4B.
There is a total of 8 windings, 4 @ 4N,
4 @ 1N.
So we could have 4 @ 36 turns and 4 @ 9
turns.
This allows the connection of windings to be as
follows :-
5 parallel windings of 36 turns
each.....................................................................1.20
ohms
4 parallel windings of 45 turns as calculated in step
29.........................................1.88 ohms
2 parallel windings of 90 turns each consisting of 2 x 45 turns in
series.................7.52 ohms
4 series windings of 45 turns each =
180turns .....................................................30.1
ohms
Only one load load
match that is suitable.
Examine 4C.
There is a total of 8
windings, 4 @ 2N, 4 @ 1N.
So we could have 4 @ 45 turns and 4 @ 15
turns.
This allows the connection of windings to be as
follows :-
6 parallel windings of 30 turns
each.....................................................................0.84
ohms
4 parallel windings of 45 turns as calculated in step
29.........................................1.88 ohms
3 parallel windings of 60 turns consisting of 45 + 15 turns
each............................3.34 ohms
2 parallel windings of 90 turns
each consisting of 2 x 45 turns in series.................7.52 ohms
4
series windings of 45 turns each = 180turns
.....................................................30.1
ohms
Choose between available options.
4A and 4C give 2
load matches between 3 and 9 ohms and thus either could be used.
4B only
gives one load match within 3 and 9 ohms and cannot be
chosen.
**Note.
4C has a match to 0.84 ohms not available in 4A, but this is unlikely to ever be
used.
4A would be easier to wind, another reason to select
4A.
**Note.
When 4A is selected, the number of secondary turns per layer
could be increased to possibly keep within the
limits
for wanted low winding losses.
48 turns give 2.1 ohms, 3.8 ohms and
8.6 ohms. OK, two matches between 3 and 9 ohms.
51 turns give 2.4
ohms, 4.3 ohms and 9.64 ohms, NOT OK , only one match between 3 and 9
ohms.
57 turns give 3.0 ohms, 5.4 ohms and 12.0 ohms, OK, two matches between
3 and 9 ohms.
60 turns give 3.4 ohms, 5.9 ohms and 13.4 ohms, OK, two matches
between 3 and 9 ohms.
Choose final option to suit nominal 4 ohms and 8 ohm
speakers which can often have average Z =3 or 6
ohms.
**Note. All turns per layer which are more the
calculated minimum tpl
will have higher winding losses.
The 4A secondary pattern with 57 turns per
layer seems suitable, but the 1.0mm wire will be a tight squeeze to
get 57
turns between the cheeks.
31. Confirm the turn selection step
30 with regard to actual available wire size.
Theoretical oa wire dia =
bobbin winding width / S turns per layer.
Select wire from tables, Cu wire
dia, mm
OPT1, oa wire dia = 62mm / 57 = 1.088 mm, so from wire
tables select 1.00mm wire
because oa dia = 1.093 approx.
57 turns occupies
62.3 mm but we would fit the turns if the entry/exit of wire ends is staggered
slightly
on each side of the bobbin.
Cu dia
...........................................................................................................................1.0mm
32. Calculate chosen secondary
option winding resistance.
List the following :-
Primary turns chosen for
Ns, no.
S wire Cu dia for chosen tpl, from wire tables, mm.
Turn length is
from step 17, mm.
No of parallel sections from option chosen to make up Ns
turns, no.
ZR for chosen S turns, no.
S
winding resistance
= Ns x TL / ( No of parallel S sections x 44,000
x wire dia x wire dia ), ohms.
OPT1, Consider 57 turns per layer, arranged for 3 parallel windings of ( 57 +
19 ) turns each.
Ns
.......................................................................................................................76
Eg,
wire Cu dia
mm...............................................................................................1.0
TL
from step 17,
mm.............................................................................................267
No
parallel S sections,
no.......................................................................................3
ZR
= 2,320 / 76 squared =
932:1...........................................................................932
Swr = 76 x 259 / ( 3 x 44,000 x 1.0 x 1.0 ) = 0.149
ohms......................................0.149 ohms.
33. Calculate S loss % for chosen option
for chosen Ns turns
Nominate the SRL, ohms.
SRL = PRL / ZR from step
32.
OPT1, SRL = 5,000 / 932 = 5.4
ohms..................................................................5.4 ohms
S loss % = 100
x Swr / ( SRL + Swr ), %.
OPT1 S loss = 100 x 0.149 / ( 0.149 + 5.4 ) = 2.69%..............................................2.69%
**Note. If the option where 45
turns per secondary layer was chosen the wire size is 1.25mm dia
and the
secondary winding losses would be lower at 2.4%.
34. Calculate total winding
losses, chosen option,
Total winding loss
% = P loss + S
loss.....................................................ttl loss,
%
P loss from step19, %
S loss from step 33, %
OPT1, P loss
from step 19,
%........................................................................2.19%
S
loss from step 33, %
..................................................................................2.69%
Total
loss = 2.19 + 2.69 =
4.96%...................................................................4.88%
35. Are total winding losses
acceptable?............................................................yes/no
OPT1,
yes,.......................................................................................................yes.
36. If yes to step 35, proceed to check
if the winding height really is practical.
37. Check the final winding height and
bobbin thickness to make sure OPT1, Total winding height including bobbin bass = 18.96. Remaining clearance = window height of 22mm - 18.96mm = 3.04mm = OK
the completed wound bobbin will fit into the
core window.
Primary layers, 16 x 0.414mm = 6.624mm.
Insulation, p to p
layers, 4 x 3 x 0.05mm = 0.6mm.
Secondary layers, 4 x 1.09mm = 4.36
mm.
Insulation P to S layers, 8 x 0.6mm = 4.8mm.
Insulation over top of
last on primary, 0.6mm.
Bobbin bass thickness, 2mm.
38. Calculate leakage inductance,
where is is considered to be
an equivalent quantity of inductance in series
with the primary load
looking into one end of the primary, with the other end
grounded.
LL =
0.417 x Np
squared x TL x { ( 2 x n x c ) + a }
1,000,000,000 x n squared x b
Where LL = leakage inductance, in
Henrys,
0.417 is a constant for all equations to work,
Np = primary
turns,
TL = average turn length around bobbin,
2 is a constant, since
there is an area at each end of a layer where leakage occurs,
n = number of
dielectrics, ie, the junctions between layers of P and S windings,
c = the
dielectric gap, ie, the distance between the copper wire surfaces in P and S
windings,
a = height of the finished winding in the bobbin,
b = the
traverse width of the winding across the bobbin.
Distances are all in mm!
OPT1,
LL = 0.417 x 2,320 x 2,320 x 267 { ( 2 x 8 x 0.7 )
+ 17.7 }
1,000,000,000 x 8 x 8 x 62
=
0.00435 Henry = 4.35 mH.
39. Is the leakage inductance
low enough?
Calculate reactance of LL at 100 kHz.
ZLL at 100kHz = L in henrys x 2 x pye x F
= L x 6.28 x 100,000Hz, ohms
OPT1,
ZLL at 100kHz =
0.00435 x 6.28 x 100,000 = 2,731 ohms .................2,731 ohms
Is ZLL
less than PRL at 100
kHz?.............................................................yes/no
Eg,
we have RL = 5,000 ohms, ZLL = 2,731 ohms at 100
kHz...................yes.
40. If answer to step 38 is yes, leakage
inductance is low enough.
41. Check that calculation
of primary turns gives less than 1.6 Tesla magnetic field strength, B,
at
full power and at 14 Hz.
B =
22.6 x V x
10,000
S x T x Np x F
where B is in Tesla,
22.6 and 10,000 are constants for all transformer
equations,
V = Vrms signal voltage across the primary, or sq.rt ( PO x PRL
)
S = core stack height,
T = core tongue width,
Np = primary
turns,
F = frequency at which B is to be measured.
All dimensions in mm!!
Eg, for 60 watts into 5k, Va-a = 547vrms.
B at 14Hz = 22.6 x
547 x 10,000 = 1.57 Tesla =
OK **Note. The above wind up is for
plain UL. If CFB windings are used, there will need to be some increase
in **Note. There is some room for bulge
in the windings as they are wound on.
55 x 44 x 2,320 x 14
some of the primary to primary insulations because the CFB windings will
be at 0V potential.
so instead of at least 2 x 0.05mm p-p insulation layers
there may be extra 2 x 0.6mm.
Wire will not lay tightly as layers are
put on and will tend to spring up across the rectangular core.
The bulge will
distribute itself from start to finish and wires will not be naturally tight in
the vertical direction
hence the importance of impregnation with varnish to
make windings adhere to each other.
43. If yes to step 42, Design is OK and
sourcing materials can be undertaken.
44. Are the wire sizes available?
.......................................................yes/no
45. If no to step 42, find
out what sizes are available, and design to
suit
these
sizes without compromises!!!
46. Draw up the bobbin winding
details for the proposed OPT No 1 ready for
the guy who is going
to wind the OPT.
Fig
6.
47. Shunt capacitance of an OPT.
There are several areas in an audio transformer where capacitance exists, and
with an OPT we are primarily interested
in the total measured capacitances
when we measure the capacitance at the anode terminals of the OPT.
There is
capacitance between primary wires in the form of the "self capacitance" of the
primary layers of wire
and between layers of wire adjacent to secondary
sections which have much lower signal voltages
and are effectively at 0V
potential.
To calculate the primary shunt capacitance in an audio transformer such as
OPT No1, refer to the above bobbin winding
layout. Neglect the self
capacitance of the primary windings; it will be such a small amount compared to
the
main shunt C between adjacent P to S interfaces.
The distance between the copper surfaces of primary and secondary layers
including the insulation thickness
of 0.6mm and the wire enamel of about
0.05mm = approx 0.7mm.
Then you must allow for the curved surface of the wire
turns so total distance = approx 0.75mm.
Capacitance between two metal
plates = ( A x K ) / ( 113.1
x d )
where
Capacitance is in pF,
A is the area
in square millimetres of the plates assumed to be of equal size,
K is the
dielectric constant of the material between the plates, air being =
1.0,
113.1 is a constant for all equations to work,
d is the distance in
millimetres between the plates and is the same for the area of the
plates.
For example, if the turn length around the wound bobbin nearest 'anode 1' =
250mm, and winding traverse width
= 62mm, then area = 250 x 62 = 15,500
sq.mm.
Let us say the K for the polyester = 2.
( The C can be measured if
unknown using metal plates of known area, and using a sample of polyester
clamped tight between the plates for the whole area. Once the C measurement
has been recorded,
the plates are set up with a very small width strips of
polyester leaving the plates the same distance apart
but with mostly air
between the plates, and the C measured again.
K = C measured with full
amount of polyester / C measured with just air. )
The d we calculated above = 0.75mm.
C in pF = 15,500 x 2 / ( 113.1 x 0.75 ) = 365.5pF.
The amount of capacitance in each P to S interface varies with turn length so
that nearest 'anode 2'
the C would be less.
But for a simple estimate of the C at each P to S interface we could say C
simply = 360pF.
The first P-S interface down from 'anode 1', or the top of the wind-up at
above the GH-IJ-KL
is at a position of 6.5 layers / 8 layers along the P
winding from the CT where the signal voltage is zero.
This positioning
results in the capacitance being subject to the impedance ratio at this
position.
Therefore the C is transformed to 360pF x (6.5 / 8) squared, = 360 x 0.66 = 237pF.
The next area of 360pF down from anode 1 appears below the sec layer GH-IJ-KL
and the impedance ratio
is (5.5 / 8) squared = 0.47 so the C due to this
interface at anode 1 = 360pF x 0.47 = 170pF.
Next down the Z ratio is above
the EF sec and = (2.5 / 8) squared = 0.098, so C = 35pF at anode 1,
then
below EF the Z ratio reduces the 360pF by (1.5 / 8) squared = 13pF.
The total
C appearing at the anode 1 connection is the sum of all these transformed
capacitances =
237pF + 170pF + 35pF + 13pF = 455pF, which is approximately what we
would measure with a capacitance
meter connected to anode 1 with CT grounded
and one end of all the secondary layers all grounded.
If the OPT No1 bobbin was used for an SE amplifier design the capacitance
would be calculated similarly
but have a total of many more calculated
values of effective capacitances seen at the ONE end of the P
winding.
Cathode Feedback use further complicates the capacitance calculation
but the effect of the capacitance
on amplifier bandwidth is effectively
reduced by the NFB because the NFB reduces the Ra of the
tubes.
If the above transformer No1 is used with a pair of KT88 in beam tetrode mode
then if
the Ra is simply about 18,000 ohms at each anode and without a load
the gain of the tube will reduce
-3dB from approximately being equal to µ of
the tube at say 500Hz at where the
capacitive reactance = Ra. Since C =
approx 445pF, then this -3dB pole
is found easily at a frequency = 159,000 /
( Ra x C in uF) = 159,000 / ( 18,000 x 0.000445 ) = 19.8kHz.
In practice this
would be about correct, and one way to measure the C shunt with a tube
is to
use a high Ra tube unloaded such as a tetrode or pentode, and work from the
observed -3dB point.
The leakage inductance will have little effect on the
unloaded response.
The capacitance and leakage inductance will react together to form a tuned
circuit and
low pass filter with an ultimate slope of more than
6dB/octave.
So rapid phase shift increase occurs as F becomes high so it is
important to minimise C and LL
to force the frequency of resonance to be as
far as possible above the audio band and where
the phase shift with loop NFB
does not cause oscillations.
Trying to establish an equivalent model of the
complex LCR offered by such a simple OPT as No1
is beyond my abilities and
there is little point to achieve such modelling. It is simply easier to
establish low values of C and LL by empirical methods and then critically
damp the HF gain
of the amp to achieve low overshoot on square waves with a
0.22 uF across the output without any R load,
while maintaining a maximal HF
pole with a solely R load.
--------------------------------------------------------------------------------------------------------------------------
METRIC WINDING WIRE SIZE
CHART
The metric winding wire sizes were kindly given to me by a
local Sydney wire and transformer parts supplier.
The original chart
contained the same copper sizes as shown for grade 1 with less enamel
thickness
and grade 3 with more enamel thickness. I only use grade 2 which is
the only grade shown in the chart below.
Grade 2 is the only grade stocked by
my supplier because it is the industry norm for 99% of high temperature rated
winding wire for electric motors and stressful industrial applications.
The
range of sizes shown are not all obtainable off the shelf, and to get some sizes
a wait for an order is involved,
so I sometimes have to design around the
wire size available, which adds to the challenge.
Anyone not used to
measuring in millimetres better start getting used to metric because here the
diameter measurement matters more than the wire guage, and there are is AWG,
SWG, BS, all very confusing,
and I don't have conversion charts so if you
work in guages and inches and feet, provide your own solutions.
Before
winding anything, make sure you have an accurate micrometer to confirm that the
size is correct.
