OUTPUT TRANSFORMER THEORY.
Content of this page :-
Function of the output transformer, ( OPT ).
How the OPT works.
Impedance and resistance transformation.
Fig1.  Equivalent model of Ultralinear output stage tubes and OPT.
Functions in the model and preferred OPT characteristics.
Test conditions for specifying OPT performance.
Description of OPT No1, wire and turns and insulation description.
Fig 2.  Cross section of bobbin winding details.
Fig 3.  Schematic of OPT No1 when used in UL with two impedance matching settings shown.
Fig 4.  Schematic of OPT No1 when used with 12.5% CFB windings and with two impedance matching settings shown.
Notes re recommended amounts of CFB to be used.
Impedance matching notes.
Table 1.  Impedance matchings available with OPT No1.
Table 2.  Recommended output tubes for OPT No1 with winding losses.
Comments about alternative tubes used with OPT No1.
Specification for OPT No1, notes re LF behaviour, power handling ability, HF behaviour, HF resonances,
and distortion.
Description of PP OPT No2.
Description of SE OPT No3.
Brief note about SE OPT No4.
      --------------------------------------------------------------------------------------------------------------

In nearly all tube power amps there are transformers required to couple the output tubes to the speaker load.
Readers may wonder just what any transformer does; they see heavy box with many terminals and there are no clues
to what happens inside.

The tubes operate with large voltage and small current changes, and the product of the current and voltage
is the power they produce, measured in watts because P = E x I.  Conventional electro-magnetic dynamic speakers require high current and low voltage. Ribbon speakers require even lower voltage and higher current and will have another transformer built into them. Electrostatic speakers have transformers built in which transform the amplifier output voltage up by perhaps 100 times, and reduce the current in the ESL to be 100 times less than at the amplifier output terminals.
But we still need an output transformer to get from the tubes which are ideally suited to supplying power to a load of several thousand ohms to an "outside world" load less than 8 ohms. 

Tubes cannot be directly connected to speakers unless we use a large number of special tubes in what are called OTL amps,
or "output transformerless" amps.
I don't hear any better music when I don't see any output transformer, more simply called an "OPT".
I have not ever bothered to build any tube power amp without an OPT. Without an OPT, the load matching in all OTL amps is quite appalling, and the tubes must work in their non linear near class B region with high levels of NFB applied to straighten out the high levels of THD/IMD and very high output resistance.
When you don't want to use an OPT, perhaps mosfets are the best device to use. Tubes were never designed to
work in OTL amps; but people force them to do so and with some risk to reliability.

So I will be discussing output transformers from my viewpoint that a well done OPT offers a completely sonically transparent
and neutral method to couple the energy from vacuum tubes to speakers. With class A triode output stages it is possible to
build amplifiers which do not need any global NFB because the THD/IMD and Rout is all low enough.

The OPT works with two separate coils of wire wound around a core made of specially made iron sheets called laminations.
The laminations are usually made from thin sheet iron which contains about 4% silicon and which has been specially rolled and
heat treated to improve the magnetic qualities we seek that are suitable for use with any frequency from 2Hz to 500kHz.
One of the two coils of wire consists of a primary winding which accepts incoming power from the tubes
which provide high voltage and low current, and has a lot of very fine wire turns using insulated wire.
The other winding is the output winding called the secondary and it has much fewer turns but of much thicker wire
to suit the higher current and lower voltage for a speaker.

When we apply a signal voltage to the primary, a varying magnetic field is set up in the iron core.
This magnetic field is shared by both primary and secondary.
A strange and mysterious electro-magnetic phenomena occurs.
Suppose we have say 500Vrms applied to 2,000 primary turns. Suppose there is a secondary of 64 turns.
We will find that a voltmeter tells us there is only 16Vrms across the secondary.
This voltage is induced into the secondary by the shared and varying magnetic field produced by the signal acting on the primary.
In fact we would find that the primary to secondary voltage ratio is proportional to the primary to secondary turn ratio.
In this case we have a 2,000 : 64 turn ratio, or 31.25, called TR, so the secondary produces ( 1 / TR ) x primary voltage.

Suppose we have an 8 ohm speaker load connected across the secondary.
The 8 ohm current = 16V / 8 = 2Amps rms. The output power = I squared x RL = 2 x 2 x 8 = 32 watts.

We will find that the current in the primary winding = secondary current  / TR = 2 / 31.25 = 0.064 Arms, or 64 mA.

Readers should be able to see that the primary input power = 500V x 0.064 = 32 watts,
because Power liberated in a load = Voltage across the load x Current flow in ther load.

They should also see that where you have 500V applied to a load at the primary where 0.064 A flows,
then from Ohm's Law, load, RL = E / I = 500 / 0.064 = 7,812 ohms.

The impedance ratio of the transformer is the change of load seen at the primary compared to the load connected at the secondary, and in the example we see that 8 ohms is transformed to 7,812 ohms at the primary.
The OPT is viewed as having no impedance or resistance itself , it is merely a device
to change the resistance or impedance
of a secondary load to suit the tubes.
The change in impedance is the impedance ratio, ZR,
and in this case ZR = 7,812 / 8 = 976.6 : 1
This is also always the square of the turns ratio and in this case the square root of the impedance ratio
= the turn ratio = 31.25 : 1.

Therefore the OPT transforms the secondary load from 8 ohms to 7.8k ohms "looking into" the OPT primary
terminals. The 7.8k load load could well suit a pair of 6550 or KT88 connected with 30% Ultralinear taps
or operating in triode mode.

Like any device used for power transformation there are technical imperfections. The winding resistance of the
wire used in the OPT may be 2.5% of the loads for each of the P and S windings and so a total of 5% of power
is lost as heat in the OPT, so that to get 32 watts at the output, we would have to apply 33.6 watts to the primary,
ie, the input to the OPT primary must be a slightly higher primary voltage since there is effectively 5%
of the primary load in series with the real primary load were we to consider the OPT as being perfect and without any
winding losses. So the total winding resistance at the P, RwP = 5% x 7.8k = 0.39k,
so the actual load connected to the tubes is 7.8k plus 0.39k = 8.19k.
During design analysis work we might neglect the Rw to keep calculations simple except for calculations of
amplifier output resistance. These are all dealt with in my 'tube operation' and 'load matching pages'.

Here is a very basic Model of output tubes and output transformer with basic resistance, capacitance, and
leakage inductance.
Fig1.
Schematic of model for basic output stage.
This is an equivalent model of a PP output stage with a pair of class A UL 6550 tubes.
The OPT is considered without its centre tap and B+ supply because we are only interested here in the ac working.
So the OPT primary with CT can be considered here as one winding with one end grounded.
The Ra of 4k for each tube is summed to make Ra-a = 8k and this output anode resistance of the2 tubes
is shown in series between OPT primary winding input and the output of an imaginary voltage generator.
The model generator has an imaginary output = µ x grid input voltage which in this case is the summed grid to grid signal input voltage of 51.85Vrms
The µ of the tubes = 20, so the generator produces the imaginary Vout = 1,037Vrms.
We know there is 500Vrms across the the primary load and the load is 7.8k, so we have 64mA of load current
and this flows around the circuit through Ra-a to the OPT input, through the leakage inductance
which appears as a series inductance, then through the winding resistance which also acts as a series resistance,
and through the transformed secondary load which appears here as 7.8k at the primary winding input.
The actual two winding transformer is considered perfect with no losses, but the imperfections are added
as they behave in the real world and are depicted as lakage inductance, LL, = 5mH,
total Primary + Secondary winding Resistance, Rw, = 390 ohms, primary shunt inductance = 100H,
and
primary shunt capacitance = 500pF.

The shunt capacitance may be calculated fairly accurately with a method shown in the page on
'PP Output Transformer Calculations'.

With most OPTs, there are numerous windings, and a far more complex number of C and L
values exist if one were to draw a full equivalent model for the OPT.

 Predicting the actual real performance outcome of a real OPT based on dimensioning the known winding details has not yet been successfully attempted on a computer.  Since output transformers are not mainstream engineering practice
nobody has bothered to produce a program which will reliably simulate the use of a known OPT design
100% accurately.

There will be some resonant behaviours which will give undulations in the response above the audio band but as long as the
leakage L and shunt C are both kept low, the queer HF response will not occur until above 75kHz, and they can be dealt
with without causing audible problems. The above model of an output stage will do for a basic understanding.
At 1kHz, the "reactive" elements of LL, Csh, Lp will have virtually no effect on load and gain.
But at very low F, the Lp becomes low impedance, and at very high F the Csh and LL begin to
act as a low pass filter and prevent any signal reaching the load.

Basically, and OPT is like an electronic gear box to couple a high revving engine with low torque to slow turning
wheels with high torque which is the case when we drive up the hill with truck load of bricks.
There are limits on the rev range, and the engine has bandwidth, like the OPT.

Now there is an odd thing about the load of bricks. The more bricks on the truck, the harder it is to make it up the hill.
But in electronics, the more ohms there are, the easier it is to sustain a voltage across the load.
That's because when you have less ohms, there is more current, because I = E / R, so with more current there is more power required.
So more ohms are easier to drive than a few ohms. Creating a voltage change without any current flow is very easy to do.
So just remember that you cannot always associate bricks and trucks and ease of doing things and common sense when you confront trying to understand anything about electricity and magnetism. At least basic mathematics will be required
to understand every basic electronic concept in one's mind. Fortunately, nearly all tube electronics can be covered with
simple high school mathematics.

I refuse to explain exactly why electro-magnetic phenomena occurs and I refuse to give all the math involved lest I bore everyone to tears, and besides, I have no room in this humble little website to include all the pages of all the old books.
Should you wish to know more about how and why the God Of  Triodes invented a universe full of rather odd rules governing electro-magnetic behaviour,
study the text books and university reading material
Excellent reference reading on output transformers can be found in the Radiotron Designer's Handbook, Fourth Edition, 1955.
Some of the information about transformers is actually comprehensible to an educated lay person, and still makes perfect sense 51 years after the book was written by that genius, Fritz Langford-Smith, who supervised the team who produced the book of 1,600 pages.
Pages 211 to 228 offer information which has all been incorporated into
the the designs of my transformers, all in keeping within the very best design traditions.
Most of the "RDH4" as I refer to it is now quite irrelevant in this digital age, but the sections with theory on
power amps and tube operation are very valid.  

So I leave those who are completely mystified by what I have said so far to read more elsewhere about the mystericals.

I am concerned with practical aspects of transformer use and their manufacture and a post graduate honours degree
in electro-magnetics won't improve my amplifiers or the quality of how I might wind an OPT.

Luckily, OPT behaviour is governed by a few simply applied formula. The performance of a given OPT is easily
calculated when the turns and geometric turn layout and core type is fully known.

The frequency response of the OPT and iron caused distortion will vary greatly depending on the output resistance of the signal
source driving the primary of any audio transformer, so neither triode or pure beam tetrode or pentode output stages should
be used for testing the specs for OPTs. Ultralinear operation is ideal because the anode resistance from anode to anode
is approximately equal to the P load.
The test conditions for the OPT specified performance should include :-
1, Tubes driving the primary have a bandwidth capability at the maximum wanted output level from 2Hz to 500kHz
into a purely resistive load and without any applied NFB.
2,  The Rout from the output tubes should be equal to the primary input load, so use 6550 wired as Ultralinear with approximately 30% screen taps.
3,  The secondary should be loaded with the rated design load resistance, usually 8ohms.

Under such drive conditions the results of testing a given OPT should be as follows :-
At full power, Saturation of the core at 16Hz, HF -3dB point at 65kHz.
At 1/16 full power, or at 1/4 of the clipping output voltage, -12dbV, Saturation at 4 Hz,
HF -3dB point at 65kHz, LF -3dB point at below 5 Hz.
For any level the resonant frequency of the shunt capacitance and leakage inductance measured at the primary input
terminals should be in excess of 100kHz.
Total winding wire resistance losses should be less than 5% of the power input to the primary.
P and S winding losses should be nearly equal. Dc winding losses will be low under such conditions.


Without further general comment, allow me to talk about the design of 2 very good push pull OPTs which would be usable
for many purposes, No1, and No2, and their possible uses with the same windings exactly, but with an air gapped gapped core for single ended operation to give No3 and No4.
I will the complete relevant details of the 4 designs here but for the actual design process there a separate page
'output transformer calculations'  which explains how I arrived at the final design.

PP OUTPUT TRANSFORMER NO1.

The Core is 3.5% Grain Oriented Silicon Steel E & I laminations, wasteless pattern.
Centre leg width = 44 mm.
Stack height = 51 mm
Weight of core = approx 4.5 Kg, or 10.2 lb.
 

The Primary winding for anodes is 0.35 mm copper dia wire.
The overall dia including the coating of insulation will be 0.42 mm.
The traverse width of 62 mm of the bobbin will allow 145 turns per layer.
There are a total of 16 primary layers each with 145 turns, to make a total of 2,320 turns.
These layers are grouped into five sections, with two sections of two layers,
and three sections of four layers.
The HT is connected to a CT and UL screens can be connected to tappings at 37.5%
of the half primary windings to provide the UL screen feedback.
The central four layers are subdivided into four separately terminated windings to allow
tertiary cathode feedback use of either 12.5% or 25% of the total windings.

The plate current rating into the CT is 570 Ma, but only 100 Ma would typically be used.
The current rating is based on 3 amps per square mm of copper area.
 

The Secondary winding for speaker connection consist of 6 windings in 4 layers using 1.0 mm copper dia wire.
Three have 57 turns each between each side of the bobbin.
The uppermost secondary layer in the wind up is divided into three sections of 19 turns each.
These four layers are alternately placed between the 5 main primary sections.
It can be seen that there are 5 primary sections, and four secondary
interleaved sections.
Thus 57, 76, and 114 secondary turns are available for matching purposes.

High temperature insulated best quality copper magnet winding wire must be used,
and neatly wound in even flat layers to fill the bobbin.

Insulation :-
Insulation can be Teflon, which is best, but it is very expensive and difficult to work with.
Polyester is quite OK and has sufficiently good temperature ratings and a dielectric constant of under 3, and very similar to Teflon so the effective capacitance is not increased too much. Don't use electrical paper. Nomex is another one which
is also OK. I have used polyethylene which gives a lower dielectric constant of less than 2, so capacitances are minimal
with polyethylene but the temperature rating is poor, so a short circuited tube may heat a primary winding and melt the insulation unless there is active protection against excessive tube currents.
Polyethylene, also known more commonly as polythene does not allow the use of electrical varnish and baking at 125C for 4 hours and the OPT must be impregnated by soaking in molten wax at less than 90C.
Alternatively use polyurethane two pack Estapol 7008 which is applied while you wind and which avoids the whole
process of varnish or wax or baking. See the page on winding transformers.

The OPT described will not run hot under normal conditions.
The insulation is placed as noted on the bobbin winding guide.
It should be pre cut from sheets to tightly fit between the cheeks of the bobbin, but not so tight to causes wrinkling of the sheet materials.
The arrangement allows for 0.05 mm thick insulation is placed between primary to primary layers with the same direct voltage potentials.
0.5 mm insulation is placed between primary and secondary layers, with the exception of placing it between primary to primary layers as shown on the winding guide within the four central layers
to allow the use of all these layers, or half of them for a tertiary cathode feedback winding.

All wires coming out of the wound bobbin through slots or holes are insulated with heat resistant sleeving cut to 50 mm long, so 25mm of the sleeving extends into the winding area. Outside the bobbin, this fine gauge sleeving extends 25 mm,
and allow for slightly larger sleeving to be fitted over the top between the bobbin
and the termination boards, following winding of the bobbin.

Fig 2.
OPT1 bobbin wind up layer details.



The schematic for the OPT No1 is shown below with probably the most common and desirable load matching
for the majority of push pull amplifiers world wide.
Fig 3.
Schematic of OPT No1.

The Fig 3 above shows the OPT connected for standard Ultralinear with 37.5% screen taps.

Fig 4.
Schematic OPT No1 with CFB.
The Fig 4 above shows the use of 12.5% of the primary windings used for cathode feedback to the output tubes.
Its possible to use all primary layers from 6 to 13 ( see Fig 2 ) to have 25% of CFB.
My website page describing the integrated 8585 amplifier shows the details for using 12.5% CFB with
KT90, KT88, 6550, with Ea = 480V, screen suppl, Eg2 = 330V. This gave the best power output, lowest THD,
and biggest effective anode resistance reduction compared to any other way of setting up an output stage for multi-grid tubes. However the maximum grid driving voltage at each output tube is 56Vrms, and using 25% CFB increases this to
about 87Vrms, and the distortion of the drive stage begins to be a problem.

The Impedance Matches available are dependant on the available turn ratios.

There are 3 main turn ratios.
(1)  2,320 primary turns to 57 secondary turns, with four paralleled 57 turn windings.
This gives a TR = 40.7:1, which gives an impedance ratio, ZR, = 1,656:1.

(2)  2,320 primary turns to 76 secondary turns, made up from three paralleled 57 turn windings, seriesed with three 19 turn windings in parallel.
This gives a TR = 30.5:1, which gives ZR = 930 to 1.

(3)  2,320 primary turns to 114 secondary turns, made up with two seriesed
pairs of 57 turn windings in parallel.
This gives a TR = 20.3:1, which gives ZR = 412:1.

Table 1.  Load matching and impedance ratios, OPT NO1.

Primary Kohms, 
2,320 turns
( 1 )
Secondary ohms,
57 turns
( 2 ) 
Secondary ohms,
76 turns
( 3 ) 
Secondary ohms,
114 turns
1.65 1.0 1.8 4.0
3.31 2.0 3.6 8.0
4.97 3.0 5.3 12.0
6.61 4.0 7.1 16.0
8.28 5.0 8.8 20.0
9.94 6.0 10.6 24.0
11.59 7.0 12.4 28.0
13.27 8.0 14.2 32.0
14.91 9.0 16.0 36.0
16.57 10.0 17.8 40.0

The winding resistances are :-
Primary, 2,320 turns of 0.35 mm dia wire = 113 ohms.
Secondary, 4 x parallel 57 turn windings, 1.0mm dia wire = 0.085 ohms = 141 ohms reflected to the primary.
Total winding resistance looking into the primary = 113 + 141 = 254 ohms.

OPT Power Loss %  = 100 x Rw / ( Rw + RL ) %

Table 2. Recommended tubes for OPT No1 with approximate power output and winding losses :-

RLa-a
Tubes
UL Class A or AB1
Ea up to 500V
Triode Class A or AB1
Ea up to 500V
Cu losses
%
1.65k
4 x KT90, KT88, 6550,
110 watts
60 watts
13.3%
3.31k
4 x KT90, KT88, 6550, 100 watts                50 watts
7.1%
4.97k
4 x KT90, KT88, 6550,
4 x EL34, 6L6GC, KT66,
2 x KT90,KT88, 6550
100 watts
85 watts
60 watts
50 watts  Ea = 480V
40 watts
30 watts
4.9%
4.9%
4.9%
6.61k
2 x KT90, KT88, 6550
4 x EL34, 6L6GC, KT66,
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
70 watts 
80 watts
35 watts
   ---                 
35 watts
30 watts
18 watts
20 watts
3.7%
3.7%
3.7%
3.7%
8.28k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
50 watts
40 watts
   ---
30 watts
25 watts
20 watts
3.0%
3.0%
3.0%
9.94k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
35 watts
35 watts
   ---
20 watts
18 watts
18 watts
2.5%
2.5%
2.5%
11.59k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
32 watts
32 watts
    ---
22.5 watts
20 watts
18 watts
2.1%
2.1%
2.1%
13.27k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
30 watts
28 watts
   ----
21 watts
18 watts
18 watts
1.9%
1.9%
1.9%
14.91k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
27 watts
26 watts
   ---
20.5 watts
16 watts
16 watts
1.7%
1.7%
1.7%
16.57k
2 x KT90, KT88, 6550
2 x EL34, 6L6GC, KT66
2 x 300B ( Ea = 450V )
26 watts
25 watts
   ---
18 watts
16 watts
16 watts
1.5%
1.5%
1.5%
The above figures give a rough approximation of maximum power at clipping that could be expected
when the multigrid tubes have Ea up to 500V, and the 300B up to 450V.
The B+ supply used and biasing levels will determine the class A % in the class AB power.
The load matching and power output and class A % and THD outcomes are covered in greater detail
in my website pages on load matching to triodes and beam tetrodes and pentodes.

There would be a considerable number of other combinations of tubes which could be built around OPT No1.
For example quads or six-packs of 6V6 or EL84 can be used for RL = 3.3k or above, but with a lower Ea of about 350V.
Where one may wish to use 6SA7 / 6080 the primary windings can be arranged so there are two parallel
windings of 1,160 turns to suit the lower RL allowable with such low impedance triodes.

The use of CFB in the OPT for the output tube cathodes does not change the load requirements from
what may be used for standard Ultralinear.

SPECIFICATIONS, OPT NO 1.

Low frequency behaviour.
The low frequency limit is due to core saturation which is voltage dependant, irrespective of load currents.
Frequency of saturation, Fsat = 13.2 Hz where Bmax = 1.8 Tesla at 547Vrms anode to anode, which
is 45 watts into 6.6k .
The primary inductance depends on the ac voltage and frequency applied and the permeability, µ, of the iron laminations.
At 50Hz maximum µ of the E&I GOSS laminations I purchase from Sankey in Newcastle, NSW, reaches 17,000 when the
lams are fully interleaved. The resulting maximum primary inductance = 1,077 Henrys.
At very low Va-a of 5Vrms, LP is greater than 100H and the inductance is entirely sufficient
so that with RL = 8ka-a and Ra-a also 8k, the -3dB point at LF at levels below saturation = lower than 6 Hz.

Power handling ability is only restricted by to whatever saturation frequency and losses are deemed acceptable, and limits on the DC input current. The primary wire size = 0.35mm dia so the maximum dc current at 3amps/sq.mm = 288mA,
or 577mA at the CT. This is much more that whatever may be used for any of the tube listed in the
recommended tube table 2 above.

110 watts into 1.65k is only 426Vrms a-a, and the ac signal current = 258mA.
This is approaching the safe continuous ac power but with music signals there is never a continuous maximum sine wave signal.

100 watts into 5k will be  707Vrms, and ac  signal current is well within the OPT safe working area.
However, as Va-a rises, the Fsat will rise, and at 800Va-a the Fsat = 19Hz, which is quite acceptable.

Winding losses rapidly increase as the RL is reduced. At RL = 5ka-a, Rw = 5% which is excellent considering the
OPT will most likely be used with loads above this figure where winding losses become negligible.

High frequency cut off.
The leakage inductance, LL,  referred to the primary = 4.2 mH. The Ra-a + RLa-a  = 8k + 8 k = 16k,
so the cut off due to LL = 606 kHz. This figure will never be seen since the shunt capacitance will cause the cut off
at a lower frequency. Cshunt looking into the end of each primary end with CT grounded and one end of the secondary
grounded will be approximately 1,000, so the equivalent Ca-a = 500pF.
The HF cut off is where the reactance of the shunt C = Ra-a and RLa-a in parallel = 4k.
Therefore HC cut off = 79.5 kHz, which is at a much lower F than than caused by the LL.

For much greater analysis of how to work out shunt capacitance see the calculations for OPT No1
in the page on 'Push Pull Output Transformer calculations'


The leakage inductance and shunt capacitance will form an initial series resonant circuit at 110 kHz when the response will
show a dip due the reduced load impedance due to the impedance of the series LC at resonance.
The dip in impedance can be reduced by a zobel network across the secondary of perhaps 8 ohms + 0.33uF.
The critical damping load required for a second order LC filter to prevent peaking in the response
= 1.41 x ZC or ZL at the resonant F. In this case, at 110kHz, 500pF has ZC = 2.9k so the damping resistance load
needed is 4k. Suppose we have the OPT set for 2,320 : 76 turns, giving a 6.6k : 7 ohms match then ZR = 932:1 so
the damping resistance theoretically should be 4k / 932 = 4.29 ohms. This is less than  the rated RL value of the amp
but 4.7 ohms could be tried with 0.47uF, thus loading the amp with a partially reactive load of 6.6 ohms at 72kHz,
and a mainly resistive load above 100kHz which should help prevent excessive response undulations.
One only needs just enough R&C for the zobel on the output to prevent excessive square wave overshoot.
The actual value of the zobel network across the secondary must be confirmed experimentally and perhaps 0.27uF and 8.2 ohms will be quite sufficient.
The phase shift and response sag at 20kHz will be negligible.

Distortion caused by the transformer is lowest at mid frequencies, and it will be tiny fraction of the total distortion produced mainly by the output tubes. But it increases with descending frequencies until it becomes suddenly severe at saturation conditions below 20 Hz when the Bmax rises above 1.5Tesla.
In practice, saturation conditions are of negligible concern if the amplifier is used sensibly. At 50 Hz, the distortion
caused by the iron hysteresis at full power is still a small fraction of the total distortion. And at 50 Hz, at 4.5 watts into 6.6k,
ie, at about 1/3 of the 45watt output voltage level, the B flux density in the transformer is 0.15 Tesla, and the transformer distortion will remain lower than the tube distortion. The grain oriented silicon steel will exhibit about ten times lower distortions than plain non oriented silicon steels at 50 Hz. DIY builders who wind their own OPT could use the non oriented steel, NOSS,
because in practice the sonic differences at low levels would be very difficult to ascertain at any level. My experience
has indicated it is impossible to tell the difference between core material that is fully grain oriented and that which has the Si content above 3% but has not been rolled and heat treated to improve the µ a further 5 times.
the non oriented E&I core material is $5 per Kg as opposed to the $12 per Kg of the GOSS.
I think the GOSS is worth the extra few dollars.
Both NOSS and GOSS steels require close to the the same number of primary turns with regard to saturation.

------------------------------------------------------------------------------------------------------------------------------

PP OUTPUT TRANSFORMER No2.

OPT 2 is larger transformer with an E&I wasteless core pattern with the same 44mm tongue dimension as with OPT No 1.
The size is simply increased by using a taller stack of laminations up to 100 mm.
The Primary turns are reduced to 2,080 total, but instead of 0.35mm dia wire, the wire diameter is 0.4 mm. The secondary wire diameter will remain 1.0 mm, and winding arrangements equal to OPT No 1. The insulation size of 0.5mm between P&S layers and else where may be reduced to 0.4mm and although this increases the Cshunt somewhat,
the RL likely to be used with such a transformer and the Ra-a will be lower so the capacitance will not reduce the
bandwidth greatly, and the slightly closer coupling distance between P&S windings will improve the leakage inductance.
All other sizes and arrangements are kept the same.
The TR available will be 36.5:1, 27.4:1, and 18.2:1, and another comprehensive array of impedance matches will be available
and most likely to suit a quad or six pack of output tubes.
My 8585 integrated amplifier design uses a 62mm stack of 44 tongue core material with 2,080 primary turns.
Four or more output tubes will be better suited to the No 2 OPT,
and another comprehensive set of impedance matches will be available.
The plate current input rating to the CT is 750mA, but 200 Ma would be
the normal working current for 4 tubes.

For both OPT1 and OPT2 the frequency performance is similarly pleasing; No 2 will go a couple of Hz lower than No1
if the stack height is 75 mm, and half an octave lower if the stack height is 100 mm.
100mm stacks of iron would be excessive imho, and begin to cause higher than wanted winding losses and
lower HF cut off.

  ---------------------------------------------------------------------------------------------------------------------------- 

SE OUTPUT TRANSFORMER NO 3

Single Ended Output transformers can be made using the same winding details as
No1 or No2, but there is an air gapped core instead of the usual maximally interleaved
laminations.
Let us consider what the OPT No1 design would be useful for were it used for an SE amplifier.

We will consider the design when used for SE to be OPT No3.

The 0.35mm dia wire will take dc current = 288 mA, at a rated 3 amps per sq.mm.
But 140 mA would be a safer figure to allow for the occasional "oops" factor when bias failure might occur.
If the B+ voltage was +500v, then power input would be 70 watts to the anode circuit. 
If Single Ended Ultralinear operation, SEUL, was called for, and maximum efficiency was 35%, then we could expect
70 x 0.35 = 24.5 watts be the maximum output power.
Load line analysis will confirm this to be the case. The load for 35% efficiency with SEUL will be one where at  clipping
the peak change in load current will be +/- approximately 0.9 x anode idle current, Iaq.

In this case it is 140mA x 0.9 = 126mA peak = 89mA rms.

ac Power in the load  = I squared x RL, where I =Amps rms.

We have PO = 24.5 watts = 0.089 x 0.089 x RL, therefore RL = 24.5  / ( 0.089 x 0.089 ) = 3,093 ohms.
The maximum load swing = 3,093 ohms x 0.089Arms = 275Vrms = + / -390V peak.

To accommodate 70watts of input power without causing undue heat stress in any output tube, and be able to operate at
Ea = 500V, we could use two KT88 or 6550 in parallel so that each was dissipating 35 watts at idle
which is well below the maximum Pda ratings of 42 watts. ( KT90 have Pda = 55 watts and would be a better choice )
The ac load seen by each tube would therefore be 2 x 3,093 = 6.19k, and even triode operation would be
quite excellent, although we would not have quite such high power maximum, but the 15 watts from triode
would be quite OK. In triode, the Ra of 2 x 6550 in triode = approx 500 ohms, so the damping factor
with RL = 3.1 = about 7, so global NFB need not be applied. UL operation will require global NFB.

With a maximum of 275Vrms signal voltage across the primary, the B at 14Hz = 0.85 Tesla.

This is a favourable result because it means that the iron could be magnetised by the dc so that the dc magnetisation
could be up to 0.75 Tesla, leaving some headroom for LF transients below 20Hz.
The Core will be able to be air gapped so that the µ is reduced from say 17,000 of the GOSS I am using to less than 1,000,
and the dc magnetization reduced.
The golden rule for SE amps is :- Reactance in ohms of the primary inductance, ZLp = RL at 20Hz or lower.
Since RL = 3.1k, Lp = 3,100 / ( 6.28 x 20 ) = 24.7H.

Experience tells me that the core could be gapped so that the measured Lp at 20 Hz = 24.7H
and the dc magnetization will not exceed 0.63Tesla.
The sum of ac and dc magnetization at 20 Hz at full power will be less than 1.63Tesla so there is plenty of headroom.
If the sum of ac and dc B < 1.6T at 14Hz, we are doing even better, and careful adjustment of the gap will
perhaps give this condition so that distortion of the LF audio signals is negligible, and bass performance is blameless.

The SE output transformer will have higher winding losses than when used for PP.
In this case since RL = 3.1k, and total winding resistance % losses = 7.8%.
Also the amount of finite leakage inductance is the same for the OPT when used for SE or PP amps
for a given winding geometry for HF.
SE Ultralinear Ra = RL approx = 3.1k, so the total series Ra + RL = 6.2k.
The LL of 4.2mH will cause a pole at 250kHz, but the shunt capacitance
of say 600pF will cause a roll off where Ra and RL are in parallel and = 3.1k, so
expect the pole for Cshunt to be at 85kHz, but resonances may affect the exact outcome.
The HF performance will be superb!
The Fo of the resonance/s may not be the same as with the PP case.
Zobel networks may be needed.

For complete design logic flow with 47 steps see my page on 'SE Output Transformer Calculations'.

SE OUTPUT TRANSFORMER No4.

The use of 2,080 primary turns of 0.4mm dia wire with a taller stack of core material
will allow a higher Ia current of about 180mA. With Ea = 500V, the Pda = 90 watts
from which we might obtain 31 watts of SEUL power to a load of about 2.5k.
So three x 6550, KT88, KT90 could be used at 30 watts Pda per tube,
or better still 4 output tubes at Pda = 22.5 watts each.
A quad of EL34, 6CA7, 6L6, 5881, KT66 could also be used but with Ea = 420Vmax.
Pda for the smaller tubes should be 20 watts max, so total = 80 watts, so
Ia could be about 190mA, load will be about 2k.  But as RL is reduced and power output increased,
winding losses increase.

The reasoning used for SE OPT No3 can all be applied.

For more calculation details go to my pages on PP OPT calculations, SE OPT Calculations.

Back to Index page